:: Volume 9, Issue 1 (9-2022) ::
2022, 9(1): 91-117 Back to browse issues page
Capacitor Voltage Comprehensive Feedback Procedure for LCL-based Grid-Connected PEMFC Power Conditioning System in a Weak and Harmonics-polluted Network
Majid Hosseinpour * , Tooraj Sabetfar
University of Mohaghegh Ardabili , Hoseinpour.majid@uma.ac.ir
Abstract:   (2668 Views)
Polymer electrolyte membrane fuel cells (PEMFC) have been considered by researchers due to their high efficiency, low pollution, and high-power density in distributed generation systems. In this paper, the connected PEMFC fuel cell power recovery system with an LCL filter is evaluated in the harmonic Grid. LCL filters, despite their greater ability to attenuate harmonics, can lead to system resonance and instability. In this research, a transformer has been used to connect the fuel cell inverter to the Grid and its leakage inductance has been used as the inductor on the network side. Besides, for optimal resonance damping, and attenuation of current ripple caused by grids voltage harmonics, capacitor voltage through feedback control has been used. Complete control of capacitor voltage feedback includes proportional, derivative, and second-order components. In the proposed control scheme, the capacitor voltage derivative component opposes the capacitor current feedback due to identical and symmetrical loop gain. Therefore, both of them can be deleted. Thus, the capacitor current sensor is saved. Instead, the LCL filter resonance is damped by a proportional component and a second-order derivative of the capacitor voltage. A low-pass filter is also added to the second-order derivative in the controllable frequency range to ensure system stability. The simulation results of the PEMFC power recovery system in different conditions confirm the proper attenuation of the grid-connected inverter, the injection of current of suitable quality into the contaminated and harmonic grid, the stability, and the appropriate dynamic response of the proposed system.
 
Article number: 5
Keywords: PEMFC inverter connected to the filter network with LCL, harmonic current attenuation, system stability, capacitor voltage through feedback control
Full-Text [PDF 3352 kb]   (1055 Downloads)    
Type of Study: Research | Subject: Power Electronics Application in Power Systems
Received: 2022/08/12 | Accepted: 2022/12/26 | Published: 2023/05/16
Send email to the article author

Add your comments about this article
Your username or Email:

CAPTCHA


XML   Persian Abstract   Print


Download citation:
BibTeX | RIS | EndNote | Medlars | ProCite | Reference Manager | RefWorks
Send citation to:

Hosseinpour M, Sabetfar T. Capacitor Voltage Comprehensive Feedback Procedure for LCL-based Grid-Connected PEMFC Power Conditioning System in a Weak and Harmonics-polluted Network. Nonlinear Systems in Electrical Engineering 2022; 9 (1) : 5
URL: http://journals.sut.ac.ir/jnsee/article-1-413-en.html


Rights and permissions
Creative Commons License This work is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License.
Volume 9, Issue 1 (9-2022) Back to browse issues page
سامانه های غیرخطی در مهندسی برق Journal of Nonlinear Systems in Electrical Engineering
نشریه سامانه‌های غیرخطی در مهندسی برق در خصوص اصول اخلاقی انتشار مقاله، از توصیه‌های «کمیته بین‌المللی اخلاق نشر» موسوم به COPE و «منشور و موازین اخلاق پژوهش» مصوب معاونت پژوهش و فناوری وزارت علوم، تحقیقات و فناوری تبعیت می‌کند.
Persian site map - English site map - Created in 0.06 seconds with 37 queries by YEKTAWEB 4657